Objective. Students explain the purpose of reduced-voltage starting, describe star-delta and part-winding starter operation, and identify the conditions under which a solid-state soft starter is selected.
When a squirrel-cage induction motor starts across the line, it draws a large inrush current — often six to eight times its full-load ampere (FLA) rating. This surge stresses the motor windings, strains mechanical couplings, causes voltage dips on the supply conductors, and can trip upstream overcurrent devices. On a limited-capacity utility service or where voltage-sensitive equipment shares the same panel, that voltage dip is unacceptable. Reduced-voltage starting methods limit inrush current by applying a lower voltage to the motor terminals at startup, then transitioning to full voltage once the motor is near running speed.
There is a trade-off: reducing voltage also reduces starting torque. Torque varies with the square of the applied voltage, so dropping voltage to 80 % cuts available torque to roughly 64 % of its across-the-line value. Selecting the right method means balancing current reduction, torque availability, cost, and the mechanical demands of the driven load.
The simplest method applies full supply voltage immediately through a magnetic motor starter. Starting current is highest (roughly 600–800 % FLA), starting torque is maximum, and equipment cost is lowest. This method suits small motors or applications where the supply system and driven machine can tolerate the inrush.
The motor windings are first connected in wye (star). In wye, each winding receives only 58 % of line voltage (line voltage divided by √3). Because torque varies with voltage squared, starting torque drops to about one-third of across-the-line torque, and line current is also reduced to approximately one-third. After a timed interval, a contactor scheme reconnects the windings in delta for normal running.
Star-delta starters require a motor designed with six accessible winding leads. The transition from wye to delta can produce a second current surge (transition transient) if not managed carefully. Open-transition starters momentarily disconnect the motor; closed-transition starters add a resistor or reactor in the circuit during switching to smooth the event. Star-delta is a cost-effective choice for loads that start unloaded or lightly loaded — centrifugal fans and pumps are common examples — where low starting torque is acceptable.
An autotransformer with taps at 50 %, 65 %, or 80 % of line voltage is placed in series with the motor at startup. The motor receives reduced voltage; after a timed interval the autotransformer is bypassed and full voltage is applied. The line current reduction is proportional to the square of the tap ratio, so a 65 % tap reduces line current to about 42 % of across-the-line inrush. Starting torque is also reduced by the square of the tap ratio. Autotransformer starters are bulkier and more expensive than star-delta units, but they allow tap selection to match torque requirements and work with standard three-lead motors. They are well-suited for high-inertia loads such as large compressors and conveyors.
Part-winding starters apply voltage to only a portion — typically half — of the motor's parallel winding circuits at startup. Starting current and torque are each reduced to roughly half of full-voltage values. A second contactor energizes the remaining windings after a short delay. Part-winding motors must be specifically designed for this method (nine-lead, part-winding design). The torque reduction may not be sufficient to start a heavily loaded machine, but the method is simple and relatively inexpensive. It is common on refrigeration compressors designed for part-winding operation.
A solid-state soft starter uses silicon-controlled rectifiers (SCRs) to ramp voltage smoothly from a preset initial value up to full line voltage over an adjustable time period. This eliminates the abrupt current surge and the mechanical shock of direct starting. Soft starters offer precise control of starting current (typically adjustable from 150 % to 400 % FLA), smooth acceleration, and often include built-in motor protection functions such as phase-loss detection and overload monitoring.
Select a solid-state soft starter when:
Soft starters do not improve power factor or running efficiency; they revert to full conduction once the motor reaches speed. For constant-speed applications where energy savings during running are also needed, a variable-frequency drive (VFD) is a separate and more capable solution.
Before working on any motor starter or control panel, apply lockout/tagout (LOTO) procedures following NFPA 70E and OSHA requirements. Verify absence of voltage with a properly rated meter. Star-delta and autotransformer starters contain capacitors or magnetic components that can hold stored energy — confirm discharge before touching internal parts. When testing soft starters, be aware that SCR assemblies can be hot after operation. Wear appropriate PPE for the arc-flash boundary established by the site's arc-flash hazard analysis. Never bypass interlocks or timing relays for convenience — they protect both the equipment and the worker.
Answer each question, then check it. Nothing is recorded; this is your own practice.
A free tech program — complimentary, as our commitment to get America working. Help us build VoTechWorks. Tell us what works, what doesn’t, and what you want to learn.
Does the school offer financial aid?
No. We don’t offer financial aid because we’re free. No, really: completely free.
Do you offer industry certification?
No. We are not certified yet, so we can’t offer that to students. What we do offer is knowledge and understanding of a trade.
Enroll first in the trade you’re interested in. You get your key, your program opens, and you begin studying.
Enroll free →