Objective. Students program a variable-frequency drive with basic parameters—motor nameplate data, acceleration/deceleration ramps, minimum and maximum frequency—and run a motor through a defined speed profile.
A variable-frequency drive (VFD) controls the speed of an AC induction motor by changing the frequency and voltage of the power it delivers. Because the synchronous speed of an AC motor is directly proportional to supply frequency, reducing frequency reduces speed; increasing frequency increases speed. This lets a single motor run a pump, fan, or conveyor at precisely the speed the process requires, saving energy and reducing mechanical wear compared with fixed-speed operation.
Rectifier section. Incoming three-phase AC (typically 208–240 V or 480 V) passes through a bridge rectifier made of diodes or SCRs. The rectifier converts AC to pulsating DC.
DC bus. Large filter capacitors (and sometimes inductors) smooth the pulsating DC into a steady DC bus voltage. The bus voltage is roughly 1.35 times the line-to-line AC input voltage. This bus is the energy reservoir the inverter draws from.
Inverter section. Six insulated-gate bipolar transistors (IGBTs) switch on and off thousands of times per second under control of the drive's microprocessor. This switching pattern is called pulse-width modulation (PWM). By varying the width and timing of the pulses, the inverter synthesizes an AC output waveform whose frequency and voltage can be set anywhere within the drive's range. The result at the motor terminals looks like variable-frequency, variable-voltage AC.
Control board. A microprocessor stores parameters, reads the keypad or remote inputs, runs protective algorithms, and drives the IGBT gate signals. This is where you enter motor data and configure operating behavior.
Before running a motor from a VFD, you must program the drive with data from the motor's nameplate. Critical entries include:
Entering incorrect nameplate data is one of the most common causes of nuisance trips and motor damage. Always read the actual nameplate; never guess.
The accel ramp (ramp-up time) defines how many seconds the drive takes to accelerate from 0 Hz to maximum frequency. A 10-second accel ramp means the output frequency rises steadily over 10 seconds. Longer ramps reduce inrush current and mechanical shock to couplings and driven equipment.
The decel ramp (ramp-down time) defines how long the drive takes to coast the output from maximum frequency down to 0 Hz. A 15-second decel ramp is longer than the accel ramp in this exercise — common in applications where a heavy load (flywheel, large fan) must be slowed gently to avoid DC-bus overvoltage trips caused by regenerative energy.
If a load decelerates too fast and pumps energy back into the DC bus faster than the drive can handle, the drive will fault on overvoltage. Extending the decel ramp or adding a dynamic braking resistor solves this.
Maximum frequency is the highest output frequency the drive will produce, typically set to 60 Hz for standard 60 Hz motors (though some applications run motors above 60 Hz when the motor and driven equipment are rated for it).
Minimum frequency keeps the motor turning slowly enough for its cooling fan to work and prevents the load from stalling. A common minimum is 6–10 Hz, though the exact value depends on the application and whether the motor has separate forced cooling.
Synchronous speed (in RPM) = (120 × frequency) ÷ number of poles.
A four-pole motor at 60 Hz has a synchronous speed of (120 × 60) ÷ 4 = 1,800 RPM. Actual shaft speed is slightly less due to slip — typically 2–4% for standard induction motors. At 30 Hz the synchronous speed of the same motor is 900 RPM; at 45 Hz it is 1,350 RPM. Measuring shaft RPM with a tachometer and comparing to the calculated synchronous speed confirms the drive is producing the commanded frequency and the motor is running normally.
VFDs store lethal DC voltage on the bus capacitors even after AC input power is removed. Always wait the manufacturer's specified discharge time (often 5–10 minutes) after de-energizing before opening the enclosure — the warning label on the drive states the required wait time. Follow your facility's lockout/tagout (LOTO) procedure: de-energize, lock out the disconnect, verify absence of voltage at the input terminals with a meter rated for the voltage class.
Wear appropriate PPE: safety glasses, insulated gloves rated for the voltage, and hearing protection if the motor and drive are run at high load. Never defeat a drive's fault or ground-fault protection during training exercises. Keep hands clear of the motor shaft and any belt or coupling while the motor is running.
Answer each question, then check it. Nothing is recorded; this is your own practice.
A free tech program — complimentary, as our commitment to get America working. Help us build VoTechWorks. Tell us what works, what doesn’t, and what you want to learn.
Does the school offer financial aid?
No. We don’t offer financial aid because we’re free. No, really: completely free.
Do you offer industry certification?
No. We are not certified yet, so we can’t offer that to students. What we do offer is knowledge and understanding of a trade.
Enroll first in the trade you’re interested in. You get your key, your program opens, and you begin studying.
Enroll free →